GSE COMP UPS 400 GSE COMP UPS 400 GSE COMP UPS 400 GSE COMP UPS 400

GSE COMP UPS is a transformer converter designed for generating a three-phase TN-C symmetrical grid A battery is connected to inverter's DC side, from which the control circuits are supplied (source 24V DC) and at the same time from which a 3-phase output voltage is directly generated, which is subsequently filtered by a passive filter and transformed to the desired voltage value.

GSE COMP UPS is an ideal product for backing up all or part of an object, e.g. continuous backup of important machines in operation.

In the case of a "micro-grid" network, or where the relevant legislation allows it, the GSE COMP UPS can be set to work in on-grid mode, like a standard on-grid inverter.

Main advantages

Features:

Basic technical data

  GSE COMP UPS 400 / 10 GSE COMP UPS 400 / 20 GSE COMP UPS 400 / 33 GSE COMP UPS 400 / 50 GSE COMP UPS 400 / 100 GSE COMP UPS 400 / 125
AC Output            
Rated AC power Pnom 10 kVA 20 kVA 33 kVA 50 kVA 100 kVA 125 kVA
Rated output current Inom 14.5 A 29 A 48 A 73 A 145 A 180 A
Maximum output current Imax (2s every 30s) 21.25 A 43.5 A 72 A 109 A 217 A 270 A
DC Input            
Rated input voltage VBATnom 750 VDC 750 VDC 750 VDC 750 VDC 750 VDC 750 VDC
Min. input voltage VBATmin 630 VDC 630 VDC 630 VDC 630 VDC 630 VDC 630 VDC
Max. input voltage VBATmax 835 VDC 835 VDC 835 VDC 835 VDC 835 VDC 835 VDC
Rated input current IINnom (at VBATnom ) 16.4 A 33 A 55 A 82 A 164 A 205 A
Dimensions (w x h x d) 600x800x350 mm 600x1100x400 mm 800x1300x500 mm 800x1800x600 mm 800x1800x600 mm 800x1800x600 mm
Weight 75 kg 150 kg 200 kg 240 kg 300 kg 300 kg

Technical data

Output voltage 3x 400 V ±10%
Efficiency ≥ 97.5 %
Output frequency 50 Hz ± 0.5 Hz
cos φ Adjustable from 0.9 capacitive to 0.9 inductive (default = 1)
Total harmonic distortion of the output current (THDi) Max. 3 % at rated current (THD of the grid ≤ 1,5%)
RFI filter Inbuilt input DC filter and output AC RFI filter
Control system 32 bit. µP DSP - TI
Communication RS 485, USB, CAN
Communication module - Optional Profibus DP, Modbus RTU, Ethernet, GSM
Contactor at the output YES
Time of disconnection from the grid if the grid is defective ≤ 10 ms
Control panel - Optional Graphic, detachable, programmable
Analog inputs 4 /0 (4) – 20 mA/ / 0 (2) – 10 V/
Analog outputs 3 /0 (4) – 20 mA/ / 0 (2) – 10 V/
Relay output 3 x relay, adjustable, programmable
Protections Current overloading, overvoltage protection of DC inputs and panels , overvoltage protection on the AC side, undervoltage, overvoltage, earth connection on the AC output, cut off between output phases, overheating of the inverter
Cooling Forced air cooling by inbuilt ventilators
Absolute altitude of the permitted usage ≤ 1000 m over the sea, at higher altitude levels reduction of the power for each 100 m of altitude reduction of the inverter power for 1 %
Relative humidity of the air ≤ 95 % without corrosive and explosive gases, without water vapor and condensates
Ambient working temperature + 0 °C to + 40 °C (-20 °C to + 40 °C with optional tempering)
Storage ambient temperature - 25 °C to + 50 °C
Protection IP20 (IP54 optional)
STN EN standards compliance Safety EN 50178
Grid quality: EN 50160
EMC emissions: EN 61000-6-2,4, EN 55011
Harmonic distortion: EN 61000–3–11, EN 61439-1,2
Instructions EEC 2014/35/EEC, 2014/ 30/EEC, 2011/65/EEC, 2015/863/EEC